Fix a Single Reader, Door or Gate That Isn't Working

Problem

Duty managers, front of house staff and site IT need to fix one reader, door or turnstile that isn't reading cards, goes red, closes too quickly, or isn't recording attendance, while the others work.

Resolution

  1. Follow your site safety procedure first

    • If entry or exit is affected, follow your site safety procedure before anything else.
    • Don't restart the access control service for a single reader.
  2. Do the basic checks

    • Check the power and cable connections.
    • Check the reader's lights and beeps.
    • Check whether nearby readers work.
  3. Check whether the swipe reaches Gladstone360

    • Swipe a known working card and check whether the swipe appears in the Gladstone360 Access module.
    • Swipe shows with a denial reason: the reader is working. The problem is the member's or staff member's set-up (membership, status, access permissions). Check the entry point profile rules (see Access Control – Entry Points and Entry Point Profiles).
    • No swipe shows: the problem is the reader, PC, network or access control service. Carry on with the next step.
  4. Check the COM port (for a reader connected to a PC)

    • Unplug the reader and plug it back in.
    • Check which COM port Windows shows the reader on, in Device Manager.
    • Check the access control configuration uses the same COM port.
  5. Monitor the reader

    • If it goes red again, note the time and monitor it.